Model SAT-ACO380 AC Load, to test three-phase voltage, current, active power, reactive power, apparent power, power factor, frequency, running time, energies of generators and UPS.

Description

AC/generator Dummy Load Tester/load Bank

SAT-ACO380 AC Load


Key Functions and Features                                                                                                                              

◆Test three-phase voltage, current, active power, reactive power, apparent power, power factor, frequency, running time, energies of generators and UPS.

◆Set/adjust discharging power according to performance parameters and detection requirements

◆Set discharging time, timing to automatic shut-off load, discharge off and alarm operator

◆Set over/under voltage protection threshold value, it can shut off load, terminate discharging and alarm user automatically.

◆Large LCD screen, friendly interface. English menu and easy operation.

◆Parallel operation function to carry out multi sets load operation by RS 485 communication

◆Built-in storage function, save 30 groups of test data, which can be inquired, deleted and put into SD card.

◆Start/stop discharging control by Serial port, and detect data real time operation etc; The storage data can be uploaded to PC by serial port or SD card, and the upper computer’s software can analyze data and pattern and print report etc.

◆Overheating and over current protection function, it can turn off load, terminate discharging and alarm automatically when over temperature and over current.

◆Set at most 5 groups power, load process automatically according to the setting power and operation time after being turned on.

 

Technical Specifications                                                                                                                                       

Mode

ACO 380/02

ACO 380/04

ACO 380/10

Working environment

Working Temperature: (-20~55)℃        

Storage Temperature: (-45~75)℃

Relative humidity: 90%(40±2℃)

Atmospheric pressure: (70~106)KPa

Working power supply

Single-phase AC220V±10, 50Hz

Load voltage

Three-phase AC380V, Single-phase AC220V

Operating power

Stand-alone: Max 20KW (Three-phase 380V)

Max 6KW (Singly-phase 220V)

Stand-alone: Max 40KW (Three-phase 380V)

Max 13KW (Singly-phase 220V)

Stand-alone: Max 100KW (Three-phase 380V)

Max 30KW (Singly-phase 220V)

Cooling mode

FCT(Fan control Temperature)

Communication Mode

RS232, RS485 and SD card

Display mode

8 inch TFT

Voltage measurement range

AC 0~450V, Display Resolution: 0.1V, Precision: ±0.5%

Current measurement range

AC 0~100A, Display Resolution: 0.1A, Precision: ±0.5%

AC 0~150A, Display Resolution: 0.1A, Precision: ±0.5%

AC 0~300A, Display Resolution: 0.1A, Precision: ±0.5%

Frequency measurement range

40~60 Hz, Display Resolution: 0.01Hz, Precision: ±0.2%

Power measurement range

0~20 KVA, Display Resolution: 0.1KVA, Precision: ±1%

0~40 KVA, Display Resolution: 0.1KVA, Precision: ±1%

0~100 KVA, Display Resolution: 0.1KVA, Precision: ±1%

Power factor measurement range

0.001~1.000, Display Resolution: 0.001, Precision: ±0.5%

Discharging Time

(0~19 hours and 59 minutes) adjustable continuously

Quantity of Parallel operation

1~99 sets

Recording Period

6~999 Seconds

Temperature measurement range

-20~100℃,Display resolution: 1℃, precision:±1℃

Insulating strength

Input≥AC1500V

Output≥AC500V

MTTF

≥50000h

Dimensions(mm)

420×500×750mm

680×600×900mm

680×600×900mm

Weight

30kg

50kg

70kg

 

 

Mode

ACO 380/20

Working environment

Working Temperature: (-20~55)℃        

Storage Temperature: (-45~75)℃

Relative humidity: 90%(40±2℃)

Atmospheric pressure: (70~106)KPa

Working power supply

Single-phase AC220V±10, 50Hz

Load voltage

Three-phase AC380V, Single-phase AC220V

Operating power

Stand-alone: Max 200KW (Three-phase 380V)

          Max 66KW (Singly-phase 220V)

Cooling mode

FCT(Fan control Temperature)

Communication Mode

RS232, RS485 and SD card

Display mode

8 inch TFT

Voltage measurement range

AC 0~450V, Display Resolution: 0.1V, Precision: ±0.5%

Current measurement range

AC 0~400A, Display Resolution: 0.1A, Precision: ±0.5%

Frequency measurement range

40~60 Hz, Display Resolution: 0.01Hz, Precision: ±0.2%

Power measurement range

0~200 KVA, Display Resolution: 0.1KVA, Precision: ±1%

Power factor measurement range

0.001~1.000, Display Resolution: 0.001, Precision: ±0.5%

Discharging Time

(0~19 hours and 59 minutes) adjustable continuously

Quantity of Parallel operation

1~99 sets

Recording Period

6~999 Seconds

Temperature measurement range

-20~100℃,Display resolution: 1℃, precision:±1℃

Insulating strength

Input≥AC1500V

Output≥AC500V

MTTF

≥50000h

Dimensions(mm)

1300×600×900mm

Weight

150kg

 

Mode

ACO 380/50

Working environment

Working Temperature: (-20~55)℃        

Storage Temperature: (-45~75)℃

Relative humidity: 90%(40±2℃)

Atmospheric pressure: (70~106)KPa

Working power supply

Single-phase AC220V±10, 50Hz

Load voltage

Three-phase AC380V, Single-phase AC220V

Operating power

Stand-alone: Max 500KW (Three-phase 380V)

          Max 160KW (Singly-phase 220V)

Cooling mode

FCT(Fan control Temperature)

Communication Mode

RS232, RS485 and SD card

Display mode

8 inch TFT

Voltage measurement range

AC 0~450V, Display Resolution: 0.1V, Precision: ±0.5%

Current measurement range

AC 0~400A, Display Resolution: 0.1A, Precision: ±0.5%

Frequency measurement range

40~60 Hz, Display Resolution: 0.01Hz, Precision: ±0.2%

Power measurement range

0~500 KVA, Display Resolution: 0.1KVA, Precision: ±1%

Power factor measurement range

0.001~1.000, Display Resolution: 0.001, Precision: ±0.5%

Discharging Time

(0~19 hours and 59 minutes) adjustable continuously

Quantity of Parallel operation

1~99 sets

Recording Period

6~999 Seconds

Temperature measurement range

-20~100℃,Display resolution: 1℃, precision:±1℃

Insulating strength

Input≥AC1500V

Output≥AC500V

MTTF

≥50000h

Dimensions(mm)

1600×1200×1650mm

Weight

350kg

 

Related Products                                                                                                                                                    

      CR-JD100.jpg     pc1.jpg

Battery Load Tester        Earth Resistance Tester          DC Ground Fault Locator

 

Why Choose Criane?                                                                                                                                            

Start from 2003

* Professional manufacturer and OEM factory.

* Independent R&D office and team. 

* 4 numbers of production line 

* ISO 9001-2000 certificate 

* High-tech enterprise proofed by government department

Excellent sales team

* Response inquiry in 30 minutes in working time, and 12 hours in off working time. 

* With professional products knowledge and oversea sales skills.  

* Always warm and thoughtful service.

4 numbers of production line.

* Clean and tidy production office.

* Military production process. 

* Humanized production management and skilled production team. 

Pre-Sales Service

* Inquiry and consulting free. 

* Sample demonstration and experience.

* Welcome to visit and inspect our Factory.

After-Sales Service

* Training how to install the machine, training how to use the machine. 

* Engineers available to service machinery locally or online.

* 15 months warranty

As a professional manufacturer and supplier of ac/generator dummy load tester/load bank for sale, we warmly welcome you to wholesale the high quality and reasonable price equipment for sale from our factory.

Related Products

Feedback

Products List
element.style { background: url(/Content/upload/201731415/201707041007287576978.jpg) center center no-repeat; }